Application Information
(4) Refrigerant Piping
When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends
increases, system piping resistance to the refrigerant ow increases, thus lowering the cooling capacity,
and as the result the font compressor may become defective. Always choose the shortest path and follow
the recommendation as tabulated below:
Model
Indoor
FDMRN25/35CXV1
FDMQN25/35CXV1
FDMRN50/60CXV1
FDMQN50/60CXV1
FDMRN71CXV1
FDMQN71CXV1
Outdoor
R(Y)N25/35CXV1
R(Y)N50/60CXV1
R(Y)N50/60CXY1
RR71CXV1
RQ71CXV1
RR71CXY1
RQ71CXY1
Max. Length, m 12 15 15 15
Max. Elevation, m 5 8 8 8
Model
Indoor
FDMRN100CXV1
FDMQN100CXV1
FDMRN125CXV1
FDMQN125CXV1
FDMRN140CXV1
FDMQN140CXV1
Outdoor
RR90/100DXV1
RQ90/100DXV1
RR90/100DXY1
RQ90/100DXY1
RR125DXY1
RQ125DXY1
RR140DXY1
RQ140DXY1
Max. Length, m 45 45 45 35
Max. Elevation, m 25 25 25 15
Piping Sizes (Flare connection type)
Piping sizes are as follows:
R410A
Model
R(Y)N25CXV1
R(Y)N35/50CXV1
R(Y)N50CXY1
R(Y)N60CXV1
R(Y)N60CXY1
RR71CXV1
RQ71CXV1
Liquid, mm / in 6.35 / 1/4 6.35 / 1/4 6.35 / 1/4 9.52 / 3/8
Suction, mm / in 9.52 / 3/8 12.70 / 1/2 15.88 / 5/8 15.88 / 5/8
Model
RR71CXY1
RQ71CXY1
RR90/100DXV1
RQ90/100DXV1
RR90/100/125DXY1
RQ90/100/125DXY1
RR140DXY1
RQ140DXY1
Liquid, mm / in 9.52 / 3/8 9.52 / 3/8 9.52 / 3/8 9.52 / 3/8
Suction, mm / in 15.88 / 5/8 15.88 / 5/8 15.88 / 5/8 19.05 / 3/4
DAIKIN_FDMRN.indb 13DAIKIN_FDMRN.indb 13 1/8/2013 8:46:04 AM1/8/2013 8:46:04 AM