Troubleshooting (OP: Schedule Timer) Si38-606
186 Troubleshooting
4. Troubleshooting (OP: Schedule Timer)
4.1
UE
Malfunction of Transmission between Central
Remote Controller and Indoor Unit
Remote
Controller
Display
UE
Applicable
Models
Schedule timer
All models of indoor units
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and centralized remote controller is
normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Malfunction of transmission between central remote controller and indoor unit
Disconnection of connector for setting master controller (or individual/combined switching
connector)
Defect of schedule timer PC board
Defect of indoor unit PC board