Daikin BRC7E65 Specifikace Strana 178

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 254
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 177
Si38-606 Troubleshooting by Indication on the Remote Controller
Troubleshooting 167
2.43
U4
Malfunction of Transmission between Indoor Units
Remote
Controller
Display
U4
Applicable
Models
All model of indoor unit
RXM8, 10M
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor and outdoor units is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Indoor to outdoor,outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
or wrong wiring
Outdoor unit power supply is OFF
System address doesn’t match
Defect of indoor unit PC board
Defect of outdoor unit PC board
Zobrazit stránku 177
1 2 ... 173 174 175 176 177 178 179 180 181 182 183 ... 253 254

Komentáře k této Příručce

Žádné komentáře