Outdoor Units • R-410A • RN-E2V1B
2
Split Sky Air • Outdoor Units
4
2 Specifications
Piping connections Liquid (OD) Diameter
(OD)
mm 6.35 6.35
Gas Diameter
(OD)
mm 12.7 12.7
Drain Diameter
(OD)
mm 18 18
Piping Length Maximum m 30 30
Additional Refrigerant Charge kg/m 0.02/>10m
Max. internunit level difference m 20.0 20.0
Heat Insulation Both liquid and gas pipes
Standard Accessories Item Installation manual
Quantity 1 1
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB,
outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Sound levels are measured in an anechoic room
Sound pressure level is a relative value, depending on the distance and acoustic
environment. For more details, please refer to sound level drawings of this chapter.
The sound power level is an absolute value indicating the power which a sound source
generates.
2-3 ELECTRICAL SPECIFICATIONS RN50E2V1B RN60E2V1B
Power Supply Name V1
Phase 1 1
Frequency Hz 50 50
Voltage V 220-240
Voltage range Minimum V -10%
Maximum V +10%
Current Nominal running current
(RLA)
Cooling
(A)
A 6.75 8.62
Starting current (cooling/heating) A 6.9 8.8
Wiring connections For Power Supply Quantity 3 3
For connection with
indoor
Quantity 4 4
Remark Included earth wiring Including earth wiring
Power Supply Intake Outdoor unit only
2-2 TECHNICAL SPECIFICATIONS RN50E2V1B RN60E2V1B