Catalog 1304-1/ Page 6 of 28
AHRI Performance Data
Table 1: AHRI Performance Data
(5)
Cooling Model 007 009 012 015
Cooling
BTUH 7200 7600 7600 9000 9000 8800 11700 11700 14000 14000
Sensible BTUH 5300 5700 5700 6000 6000 5900 7800 7800 9400 9400
EER 11.7 11.5 11.5 11.1 11.1 11.1 10.3 10.3 9.6 9.6
Volts 115 230/208 265 115 230/208 265 230/208 265 230/208 265
FLA 7.5 4.1 3.6 8.9 4.7 4.2 6.2 5.4 7.3 6.3
Watts 620 660 660 810 810 790 1140 1140 1460 1460
Hydronic
Heat
Valve & Fan Motor Amps n/a 0.4 0.37 n/a 0.4 0.37 0.4 0.37 0.3 0.31
Min. Circuit Amps 8.9 4.8 4.2 10.7 5.6 4.9 7.4 6.4 8.8 7.6
Hot Water BTUH 14300 / 13800 14300 / 13800 14300 / 13800 15200 / 13800
Steam BTUH 19500 / 19400 19500 / 19400 19500 / 19400 20600 / 20500
Time Delay Fuse 15A 15A 15A 15A 15A 15A 15A 15A 15A 15A
NEMA Receptacle 5-15R 6-15R n/a 5-15R 6-15R n/a 6-15R n/a 6-15R n/a
Airow
High Low n/a High Low
n/a High Low High Low
Cool - Wet Coil 315 280 n/a 315 280 n/a 315 280 350 315
Heat - Dry Coil 335 300 n/a 335 300 n/a 335 300 370 335
Vent 70 56 n/a 70 56 n/a 70 56 70 56
Note:
Actual Vent performance will vary with application and installation conditions.
Dehumidication (pints/hr)
1.7 1.7 1.7 2.2 2.2 2.2 3.6 3.6 4.4 4.4
Net Weight (lbs) 103 103 103 107 107 107 107 107 118 118
Ship Weight (lbs)
118 118 118 122 122 122 124 124 135 135
Cabinet/Wall Sleeve (lbs) 36 36 36 36
Notes:
1. Based on ASHRAE and AHRI test conditions of 95°F DB/75°F WB outside, 80°F DB/67°F WB inside.
2. Based on ASHRAE and AHRI test conditions of 47°F DB outside, 70°F DB inside.
3. All 265 volt models must use a sub-base or be hard-wired with a disconnect switch.
4. Water – Based on ASHRAE and AHRI test conditions of 200°F EWT, 180°F LWT, 70°F EAT with a 1.8 gpm ow rate.
5. Over current protection for all units is 15 amps.
6. Overcurrent protection on 265 volt models must be cartirdge-style time-delay fuses (included and factory installed on all 265 volt chassis.
7. Cooling Full Load Amps includes Compressor, IDF and ODF FLA’s.