Outdoor Unit • Optimized for seasonal efficiency • RZQG-L7V1
1
2
Split - Sky Air
®
• Outdoor Unit
8
2 Specifications
Notes
(1) Cooling: return air temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent refrigerant piping length 5m (horizontal)
(2) Heating rated condition (Return air temperature: 20ºCDB, outdoor temperature: 7ºCDB, 6ºCWB, Equivalent ref.piping:5.0m\<horizontal\>, Front 1m, Height 1.5m)
(3) Minimum piping length: no limit
(4) PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
(5) Equipment complying with EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-
voltage system with input current \> 16A and 75A per phase
(6) Short-circuit power
(7) See separate drawing for electrical data
(8) 3 with re-charging
Piping connections Liquid Quantity 1
Type Flare connection
OD mm 9.52
Gas Quantity 1
Type Flare connection
OD mm 15.9
Drain Quantity 5
Type Hole
ID mm -
OD mm 26
Piping length OU - IU Min. m 5 (5)
Max. m 50 75
System Equival
ent
m70 90
Chargel
ess
m30
Additional refrigerant charge kg/m see installation manual 4P302555-1
Level difference IU - OU Max. m 30.0
IU - IU Max. m 0.5
Heat insulation Both liquid and gas pipes
Defrost method Pressure equalising
Defrost control Sensor for outdoor heat exchanger temperature
Safety devices Item 01 High pressure switch
02 Fan motor thermal protection
03 Fuse
2-3 Electrical Specifications RZQG71L7V1 RZQG100L7V1 RZQG125L7V1 RZQG140L7V1
Power supply Name V1
Phase 1~
Frequency Hz 50
Voltage V 220-240
Voltage range Min. % 10
Max. % 10
Current Zmax List Complies to EN61000-3-11
Recommended fuses A 25 40
Wiring connections For power supply Remark see installation manual 4P302555-1
For connection with
indoor
Remark see installation manual 4P302555-1
Power supply intake Outdoor unit only
2-2 Technical Specifications RZQG71L7V1 RZQG100L7V1 RZQG125L7V1 RZQG140L7V1