Operation Manual
for
Transmission Monitor RSUK0919
ENGLISH
CHINESE
JAPANESE
AFTER SALES SERVICE DIVISION
GLOBAL SERVICE DEPT,
ORSUK0919
Zobrazit stránku 0
1 2 3 4 5 6 ... 30 31

Shrnutí obsahu

Strany 1 - Transmission Monitor RSUK0919

Operation ManualforTransmission Monitor RSUK0919ENGLISHCHINESEJAPANESEAFTER SALES SERVICE DIVISIONGLOBAL SERVICE DEPT,ORSUK0919

Strany 2

96. Transmission Monitor display Since the number of letters to display on the LCD of Transmission Monitor is limited, abbreviations are used to displ

Strany 3

106-2 Contents of line 2 to 4 Line 2 through 4 displays data received. However, since the position to display the data received is specified (for exam

Strany 4

11 6-4 Meaning of Abbreviation Transmission from outdoor unit to indoor unitAbbreviationsin English MeaningAbbreviationsin EnglishMeaning Active ON

Strany 5 - 1㧚Application

127. Problem diagnosis Since the respective model has its own characteristics, all problem diagnosis cannot be described in details. This chapter desc

Strany 6

13 Procedure of Indoor Unit Diagnosis If LED-B (green) on indoor unit P

Strany 7

14NGOKNOOKYESYESNGNOONBlinksIs LED-A turned on by turning thepower supply back on? Is indoor unit data displayed with transmissionmonitor

Strany 8

15YESNOOKNGNOYESDoes the fuse on indoor unit PC boardor power supply line, etc. hascontinuity? Replace the fuse. (Probe possible causes of melt d

Strany 9 - 5. Operation method

16Replace indoor unit PC board. Malfunction 7-3: Indoor Unit LED-B OnPossible causesԘ Faulty indoor unit PC board(Reference) LED-B displays t

Strany 10

17YESNONOYESIs outdoor unit data displayed withtransmission monitor connected toterminal board of indoor unit? ࡮Faulty outdoor unit PC board ࡮

Strany 11

18Blinks (normal) NGOKNOOKYESYESNGNOONOFFIs outdoor unit data displayed with transmission monitor connected to terminal board of either indoor or outd

Strany 12 - 6-4 Meaning of Abbreviation

1Operation Manual forTransmission Monitor RSUK0919 DAIKIN INDUSTRIES, LTD.AFTER SALES SERVICE DIVISION GLOBAL SERVICE DEPT,

Strany 13 - 7. Problem diagnosis

19OKYESNGYESNONGNOYESNOOKOFFBlinksIs LED-A turned off by turningpower supply back on? Is correct power supply voltage supplied? Does LED-A blink right

Strany 14

20࡮Faulty transmission wire ࡮Faulty indoor unit PC board ࡮Incorrect combination of indoor and outdoor units (Note 1) This No.2 means that the wi

Strany 15 - causes

21NOYESYESNOYESNGOKIs correct voltage supplied to bothindoor and outdoor units? Recheck the power supply. NODisconnect No.2 transmission wire

Strany 16 - (Reference)

22NOYESError code “U4” is displayed on thetransmission monitor at all times. Temporary transmission error is possible.Wait for the malfu

Strany 17

23YESNOOKYESNOIs the unit operating beyond thespecified range? Explain the specified range for continuous operation to improve the operating cond

Strany 18

24NOOKNGOKNGOKIs value of each temperature thermistor close to measured value? Securely connect the connectors to check operation.YESIs abnormal value

Strany 19

25NOYESNONGOKNONGOKIs value of each temperature thermistorclose to measured value?Replace the thermistor. (If the malfunction is not remedied even whe

Strany 20

26㧺㧳OKOK㧺㧳OKNGOKIs indoor unit set to desired operatingmode? (Note) Change the operating mode, set temperature, etc. NGIs value of each temper

Strany 21

27Malfunction 7-12: Problem Diagnosis for Twin/Triple/Double twin multi-unit of Skyair using a R22 refrigerantPossible causeThis system is provid

Strany 22

28Malfunction 7-13: Water leakage occurs under a certain condition. Possible causesIt may be difficult to reproduce water leakage under a cer

Strany 23

2Contents1㧚Application ...

Strany 24

29Malfunction 7-14: Noise occurs from compressor (main unit).Possible causesIt may be difficult to reproduce abnormal noise from compressor at fa

Strany 25

308. Check method of microcomputer software version built in transmission checker When supplying power for the Transmission Monitor by pushing the IN/

Strany 26

3Transmission Monitor has advantages as follows, which will allow to prevent incorrect diagnose and reduce man-hours for maintenance. 1. Ma

Strany 27

41㧚ApplicationThis operation manual describes Transmission Monitor RSUK0919 (hereinafter referred to the Transmission Monitor) developed by Daikin Ind

Strany 28 - cause

5Applicable/non-applicable model list Example of applicable model (room air conditioner) Example of non applicable model (room air conditioner) Model

Strany 29

6Figure 1 Figure 2 Figure 3 TC㧦Transmission circuit RC㧦Receiving circuit Transmitting photo triac Receiving photo-coupler

Strany 30

74. Connection method to product Basically, Transmission Monitor should be connected to the communication wires (3 wires) of indoor and outdoor units.

Strany 31

85. Operation method Turn the power on to the product after connecting the Transmission Monitor according to “4.Connection method to product". Af