EDUS 04-740 ENGINEERING DATA SPLIT D-Series - Heat Pump -
Specifications, designs and other content appearing in this brochure are current as of February 2007 but subject to change without notice.
EDUS04-740
Printed in U.S.A. 02/2007 B AK
EDUS 04 - 740
D-Series
- Heat Pump -
Zobrazit stránku 0
1 2 3 4 5 6 ... 123 124

Shrnutí obsahu

Strany 1 - - Heat Pump

1645 Wallace Drive, Suite 110Carrollton, [email protected] 04-740 ENGINEERING DATA SPLIT D-Series - Heat Pu

Strany 2 - Room Air Conditioners

EDUS04-740 DimensionsRoom Air Conditioners D-Series 9FTXS24DVJULEFT2-5/16WIRELESS REMOTE(ARC433A53)CONTROLLERTHE MARK (®) SHOWS PIPING DIRECTIONREARFL

Strany 3 - EDUS04-740

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 99

Strany 4 - 1. Power Supply

Operation Manual EDUS04-740100 Room Air Conditioners D-SeriesPress SILENT button again.Press SILENT button.

Strany 5 - 2. Functions

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 101

Strany 6 - 3. Specifications

Operation Manual EDUS04-740102 Room Air Conditioners D-Series

Strany 7 - 60Hz 230V

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 103

Strany 8

Operation Manual EDUS04-740104 Room Air Conditioners D-Series

Strany 9 - 4. Dimensions

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 105

Strany 10 - FTXS24DVJU

Operation Manual EDUS04-740106 Room Air Conditioners D-Series

Strany 11 - 4.2 Outdoor Units

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 107

Strany 12 - RX24FVJU

Operation Manual EDUS04-740108 Room Air Conditioners D-Series

Strany 13 - 5. Wiring Diagrams

Dimensions EDUS04-74010 Room Air Conditioners D-Series4.2 Outdoor UnitsRX09/12FVJURX15/18FVJU6-1/21-15/161/24-1/85/1621-5/82-1/211-1/44-1/811-13/163-1

Strany 14 - 5.2 Outdoor Units

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 109

Strany 15 - 6. Piping Diagrams

Operation Manual EDUS04-740110 Room Air Conditioners D-Series

Strany 16 - 6.2 Outdoor Units

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 111

Strany 17 - RX15/18FVJU

Operation Manual EDUS04-740112 Room Air Conditioners D-Series

Strany 18 - 7. Capacity Tables

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 1133P141693-2KARC433A53Cancels timer setting

Strany 19 - Capacity Tables EDUS04-740

Optional Accessories EDUS04-740114 Room Air Conditioners D-Series13.Optional Accessories13.1 Option List13.1.1 Indoor UnitsNote: +1 Wiring adapter is

Strany 20 - EDUS04-740 Capacity Tables

EDUS04-740 Optional AccessoriesRoom Air Conditioners D-Series 11513.2 Installation Manual13.2.1 KRP413A1S1. Functions and Features On/Off setting Sw

Strany 21

Optional Accessories EDUS04-740116 Room Air Conditioners D-SeriesInstallationThis product is available in two types. The KRP413A1S · KRP413AA1S is fo

Strany 22

EDUS04-740 Optional AccessoriesRoom Air Conditioners D-Series 117Wiring1. Wiringc Connect one end of the wiring to connector S21 of the PCB in theindo

Strany 23

Optional Accessories EDUS04-740118 Room Air Conditioners D-Series2P031616-1BTest Operation and Confirmation1. When the System is Not WorkingIs the air

Strany 24 - 8. Operation Limit

EDUS04-740 DimensionsRoom Air Conditioners D-Series 11RX24FVJUHANDLE4-HOLES FOR ANCHOR BOLTS13-3/4133/8(M8 OR M10)(I.D. φ5/8 HOSE FOR CONNECTION)1 11-

Strany 25 - 9. Sound Level

EDUS04-740 Optional AccessoriesRoom Air Conditioners D-Series 11913.2.2 KRP928B2SSafety PrecautionszRead these Safety Precautions carefully to ensure

Strany 26 - 9.2 Octave Band Level

Optional Accessories EDUS04-740120 Room Air Conditioners D-Series4.Switch Settings5.Control Codes7.Combining Equipment6.Read Operating / Error Display

Strany 27 - Sound Level EDUS04-740

EDUS04-740 Optional AccessoriesRoom Air Conditioners D-Series 12113.2.3 KPW937A43P157704-2Ab)Checking the partsInstallation of LouverCAUTIONLouver1pie

Strany 28 - 9.2.2 Outdoor Units

Optional Accessories EDUS04-740122 Room Air Conditioners D-Series13.2.4 KPW945A43P089958-2CCheck the following parts Installation Procedure Before i

Strany 29

1645 Wallace Drive, Suite 110Carrollton, [email protected] 04 - 740D-Series- Heat Pump -EDUS 04-740 ENGINEERING DAT

Strany 30 - 10.Electric Characteristics

Wiring Diagrams EDUS04-74012 Room Air Conditioners D-Series5. Wiring Diagrams5.1 Indoor UnitsFTXS09/12DVJUFTXS15/18/24DVJULED1PCB2PCB3H1PINTELLIGENT-E

Strany 31 - 11.Installation Manual

EDUS04-740 Wiring DiagramsRoom Air Conditioners D-Series 135.2 Outdoor UnitsRX09/12FVJURX15/18/24FVJUTO INDOOR UNIT60Hz 208/230V~POWER SUPPLYL2L1NOTE1

Strany 32 - Installation Tips

Piping Diagrams EDUS04-74014 Room Air Conditioners D-Series6. Piping Diagrams6.1 Indoor UnitsFTXS09/12DVJU FTXS15/18/24DVJUFIELD PIPINGFIELD PIPING(3/

Strany 33 - • Remove the screws on the

EDUS04-740 Piping DiagramsRoom Air Conditioners D-Series 156.2 Outdoor UnitsRX09FVJURX12FVJU3/8CuT3/8CuT9/32CuT9/32CuTTHERMISTORDISCHARGE PIPEOUTDOOR

Strany 34 - Intelligent-eye

Piping Diagrams EDUS04-74016 Room Air Conditioners D-SeriesRX15/18FVJURX24FVJUOUTDOOR UNIT1/2CuT1/2CuT5/16CuT5/16CuT5/16CuT5/16CuT5/16CuT5/16CuT5/16Cu

Strany 35 - Indoor Unit Installation

EDUS04-740 Capacity TablesRoom Air Conditioners D-Series 177. Capacity TablesFTXS09DVJU + RX09FVJU (60Hz 208/230V) Cooling Heating3D057579INDOOR OUTDO

Strany 36 - Mounting plate

Capacity Tables EDUS04-74018 Room Air Conditioners D-SeriesFTXS12DVJU + RX12FVJU (60Hz 208/230V) Cooling Heating3D057580INDOOR OUTDOOR TEMPERATURE(°FD

Strany 37 - 6. Drain piping

EDUS04-740Room Air Conditioners D-Series 1Split-SystemRoom Air ConditionersD-Series1. Power Supply ...

Strany 38 - Refrigerant piping work

EDUS04-740 Capacity TablesRoom Air Conditioners D-Series 19FTSX15DVJU + RX15FVJU (60Hz 208/230V) Cooling Heating3D057581INDOOR OUTDOOR TEMPERATURE(°F

Strany 39 - Trial Operation and Testing

Capacity Tables EDUS04-74020 Room Air Conditioners D-SeriesFTXS18DVJU + RX18FVJU (60Hz 208/230V) Cooling Heating3D057582INDOOR OUTDOOR TEMPERATURE(°F

Strany 40

EDUS04-740 Capacity TablesRoom Air Conditioners D-Series 21FTXS24DVJU + RX24FVJU (60Hz 208/230V) Cooling Heating3D057583INDOOR OUTDOOR TEMPERATURE(°FD

Strany 41 - Intelligent-eye sensor

Capacity Tables EDUS04-74022 Room Air Conditioners D-Series7.1 Capacity correction factor by the length of refrigerant piping (Reference)The cooling a

Strany 42

EDUS04-740 Operation LimitRoom Air Conditioners D-Series 238. Operation LimitRX09/12/15/18/24FVJU114.8Outdoor temp.(°FDB)104122866832501450Indoor temp

Strany 43

Sound Level EDUS04-74024 Room Air Conditioners D-Series9. Sound Level9.1 Measuring LocationNote: 1. Operation sound is measured in an anechoic chamber

Strany 44

EDUS04-740 Sound LevelRoom Air Conditioners D-Series 259.2 Octave Band Level9.2.1 Indoor UnitsFTXS09DVJUFTXS12DVJUFTXS15/18DVJUCOOLINGNC-40NC-30NC-50N

Strany 45

Sound Level EDUS04-74026 Room Air Conditioners D-SeriesFTXS24DVJUCOOLINGNC-40NC-30NC-50NC-60NC-20POWER SOURCEJIS STANDARD OPERATING CONDITIONSOCTAVE

Strany 46

EDUS04-740 Sound LevelRoom Air Conditioners D-Series 279.2.2 Outdoor UnitsRX09FVJURX12FVJURX15/18FVJUCOOLINGNC-40NC-30NC-50NC-60NC-20POWER SOURCEJIS S

Strany 47 - Run Test and Final Check

Sound Level EDUS04-74028 Room Air Conditioners D-SeriesRX24FVJUCOOLINGNC-40NC-30NC-50NC-60NC-20POWER SOURCEJIS STANDARD OPERATING CONDITIONSOCTAVE BA

Strany 48 - Safety Precautions

EDUS04-7402 Room Air Conditioners D-Series13.2 Installation Manual ...115

Strany 49 - Precautions on Installation

EDUS04-740 Electric CharacteristicsRoom Air Conditioners D-Series 2910.Electric Characteristics3D056378Representative Unit Combination Power Supply CO

Strany 50 - 0.22 oz/ft

Installation Manual EDUS04-74030 Room Air Conditioners D-Series11.Installation Manual11.1 Indoor Units11.1.1 Safety PrecautionsSafety Precautions• Rea

Strany 51 - Outdoor Unit Installation

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 3111.1.2 09/12 ClassAMounting plate1CAir-purifying filter with photocatalytic deodorizing

Strany 52

Installation Manual EDUS04-74032 Room Air Conditioners D-SeriesAir filters F (M1/8” X 13/16”L) E Remote controller holder D Wireless remote controlle

Strany 53 - Pump Down Operation

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 33Intelligent-eye sensor1. Adjusting the angle1) Once installation of the indoor unit is

Strany 54 - Good Wrong

Installation Manual EDUS04-74034 Room Air Conditioners D-SeriesIndoor Unit Installation1. Installing the mounting plate• The mounting plate should be

Strany 55

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 35Wire guideWhen stripping the ends of interconnecting wires in advance, bind right ends

Strany 56

Installation Manual EDUS04-74036 Room Air Conditioners D-Series4. Wiring1) Strip wire ends (9/16in).2) Match wire colours with terminal numbers on ind

Strany 57 - Installation Guidelines

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 371. Flaring the pipe end1) Cut the pipe end with a pipe cutter.2) Remove burrs with the

Strany 58

Installation Manual EDUS04-74038 Room Air Conditioners D-Series3P141697-1G1. Trial Operation and Testing.1-1 Measure the supply voltage and make sure

Strany 59

EDUS04-740 Power SupplyRoom Air Conditioners D-Series 31. Power SupplyNote: Power Supply Intake ; Outdoor UnitIndoor Units Outdoor Units Power SupplyT

Strany 60

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 3911.1.3 15/18/24 ClassAccessoriesChoosing a SiteInstallation TipsAMounting plateERemote

Strany 61

Installation Manual EDUS04-74040 Room Air Conditioners D-SeriesIndoor Unit Installation DrawingsWrap the insulation pipe with the finishing tape from

Strany 62

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 41Indoor Unit Installation1. Installing the mounting plate. The mounting plate should be

Strany 63 - 12.Operation Manual

Installation Manual EDUS04-74042 Room Air Conditioners D-SeriesIndoor Unit Installation2. Boring a wall hole and installing wall embedded pipe.• For w

Strany 64

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 43Indoor Unit Installation3) Shape the refrigerant pipe along the pipe path marking on th

Strany 65 - 12.2 09/12 Class

Installation Manual EDUS04-74044 Room Air Conditioners D-SeriesIndoor Unit Installation5. When connecting to an HA system.1) Remove the front grille.

Strany 66

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 451.Flaring the Pipe End1) Cut the pipe end with a pipe cutter.2) Remove burrs with the c

Strany 67 - ARC433A51

Installation Manual EDUS04-74046 Room Air Conditioners D-Series3P141697-2GRun Test and Final Check1. Trial Operation and Testing.1-1 Measure the suppl

Strany 68

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 4711.2 Outdoor Units11.2.1 Safety PrecautionsSafety Precautions• Read these Safety Precau

Strany 69

Installation Manual EDUS04-74048 Room Air Conditioners D-Series11.2.2 09/12 ClassAccessories supplied with the outdoor unit:Accessories1 (A) Installat

Strany 70 - RX09/12FVJU Only

Functions EDUS04-7404 Room Air Conditioners D-Series2. FunctionsCategory FunctionsFTXS09·12DVJURX09·12FVJUFTXS15·18·24DVJURX15·18·24FVJUCategory Funct

Strany 71

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 49• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust air

Strany 72

Installation Manual EDUS04-74050 Room Air Conditioners D-SeriesOutdoor Unit Installation1. Installing Outdoor Unit1) When installing the outdoor unit,

Strany 73

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 51Outdoor Unit Installation• If adding additional refrigerant, perform air purging from t

Strany 74

Installation Manual EDUS04-74052 Room Air Conditioners D-SeriesIn order to protect the environment, be sure to pump down when relocating or disposing

Strany 75

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 53Wiring Do not turn ON the safety breaker until all work is completed.1)Strip the insul

Strany 76

Installation Manual EDUS04-74054 Room Air Conditioners D-Series3P141697-3GRun Test and Final Check1. Trial Operation and Testing.1-1 Measure the suppl

Strany 77

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 5511.2.3 15/18/24 ClassPrecautions on InstallationPrecautions for Selecting the Location1

Strany 78

Installation Manual EDUS04-74056 Room Air Conditioners D-Series• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust air

Strany 79

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 571.Installing Outdoor Unit1) When installing the outdoor unit, refer to “Precautions for

Strany 80

Installation Manual EDUS04-74058 Room Air Conditioners D-Series*1. Pipe length vs. vacuum pump run time*2. If the vacuum pressure gauge pointer swings

Strany 81

EDUS04-740 SpecificationsRoom Air Conditioners D-Series 53. Specifications60Hz 230VNote:  The data are based on the conditions shown in the table bel

Strany 82

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 59Outdoor Unit InstallationIn order to protect the environment, be sure to pump down when

Strany 83

Installation Manual EDUS04-74060 Room Air Conditioners D-SeriesWiring3)Pull the wire and make sure that it is tight. Then fix the wire in place with a

Strany 84

EDUS04-740 Installation ManualRoom Air Conditioners D-Series 613P141697-4GRun Test and Final Check1.Trial Operation and Testing.1-1 Measure the supply

Strany 85

Operation Manual EDUS04-74062 Room Air Conditioners D-Series12.Operation Manual12.1 Safety precautions

Strany 86

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 63

Strany 87

Operation Manual EDUS04-74064 Room Air Conditioners D-Series12.2 09/12 Class

Strany 88

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 65

Strany 89 - ARC433A51

Operation Manual EDUS04-74066 Room Air Conditioners D-Series ARC433A51

Strany 90 - 12.3 15/18/24 Class

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 67

Strany 91

Operation Manual EDUS04-74068 Room Air Conditioners D-Series

Strany 92

Specifications EDUS04-7406 Room Air Conditioners D-Series60Hz 230VNote:  The data are based on the conditions shown in the table below.ModelIndoor Un

Strany 93

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 69RX09/12FVJU OnlyOperation outside humidity or temperature range may cause a safety device

Strany 94

Operation Manual EDUS04-74070 Room Air Conditioners D-Series

Strany 95

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 71

Strany 96

Operation Manual EDUS04-74072 Room Air Conditioners D-Series

Strany 97

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 73

Strany 98

Operation Manual EDUS04-74074 Room Air Conditioners D-Series

Strany 99

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 75Press SILENT button.Press SILENT button again.

Strany 100 - EDUS04-740 Operation Manual

Operation Manual EDUS04-74076 Room Air Conditioners D-Series

Strany 101 - Press SILENT button

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 77

Strany 102

Operation Manual EDUS04-74078 Room Air Conditioners D-Series

Strany 103 - Operation Manual EDUS04-740

EDUS04-740 SpecificationsRoom Air Conditioners D-Series 760Hz 230VNote:  The data are based on the conditions shown in the table below.ModelIndoor Un

Strany 104

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 79

Strany 105

Operation Manual EDUS04-74080 Room Air Conditioners D-Series

Strany 106

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 81

Strany 107

Operation Manual EDUS04-74082 Room Air Conditioners D-Series

Strany 108

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 83

Strany 109

Operation Manual EDUS04-74084 Room Air Conditioners D-Series

Strany 110

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 85

Strany 111

Operation Manual EDUS04-74086 Room Air Conditioners D-Series

Strany 112

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 87

Strany 113

Operation Manual EDUS04-74088 Room Air Conditioners D-Series3P141693-1KARC433A51Cancels timer setting

Strany 114 - Cancels timer setting

Dimensions EDUS04-7408 Room Air Conditioners D-Series4. Dimensions4.1 Indoor UnitsFTXS09/12DVJUFTXS15/18DVJUTHE MARK (®) SHOWS PIPING DIRECTIONWIRELES

Strany 115 - 13.Optional Accessories

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 8912.3 15/18/24 Class

Strany 116 - CAUTION

Operation Manual EDUS04-74090 Room Air Conditioners D-Series

Strany 117 - 2. KRP413A1

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 91ARC433A53

Strany 118 - 1. Wiring

Operation Manual EDUS04-74092 Room Air Conditioners D-Series

Strany 119 - 2P031616-1B

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 93

Strany 120 - 13.2.2 KRP928B2S

Operation Manual EDUS04-74094 Room Air Conditioners D-Series RX15/18/24DVJNOTE: A breaker must be turned on for 24 hours before the operation start i

Strany 121 - 7.Combining Equipment

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 95

Strany 122 - I Installation Procedure

Operation Manual EDUS04-74096 Room Air Conditioners D-Series

Strany 123 -  Before installation

EDUS04-740 Operation ManualRoom Air Conditioners D-Series 97

Strany 124

Operation Manual EDUS04-74098 Room Air Conditioners D-Series